Tent Weights: How Much Ballast a Rental Tent Needs Per Leg

Event tent weights run to hundreds of pounds per leg, not the 40 pound bags sold for pop up canopies. TentCraft rates its frame tents with 625 pounds at every leg, and American Tent puts a 40x60 frame tent on 40 water barrels of 660 pounds, 26,400 pounds in all. The fire code requires anchorage that withstands the weather.

  • 19 min read
  • Written by Rentopus

Key takeaways

  • The 2024 International Fire Code, section 3103.8 as adopted in the 2025 California Fire Code, requires tents to be "designed and installed to withstand the elements of weather and prevent collapsing", with documentation furnished to the fire code official.
  • Water filled ballast is allowed only where approved and in line with the tent maker's load specifications (section 3103.8.1). Laconia, New Hampshire prohibits water barrels on any tent over 400 square feet unless they supplement another approved method.
  • TentCraft's engineer stamped reports rate its 10x10 to 20x20 frame tents at 50 to 100 mph with 625 pounds per leg, depending on size and sidewalls.
  • American Tent's water barrel weighs 30 pounds empty and 660 full. A 20x20 takes 8 barrels, a 40x60 takes 40: about 3,000 gallons of water to fill on site.
  • San Francisco's fire department requires at least 5 pounds of ballast per square foot of tent, 10 on Port property, held with 2 inch ratchet straps rather than rope.
  • TentCraft's engineers count one properly installed stake as equal to about 200 pounds of weight.

Go to section

Sections 1 to 11
  1. What the fire code says about anchoring a tent
  2. Stakes or ballast
  3. How much weight per tent leg
  4. Local rules that set the number
  5. Types of tent ballast and what they weigh
  6. Wind ratings and when to take a tent down
  7. How to anchor a tent on concrete or asphalt
  8. Canopy tent weights: the 10x10 question
  9. Canada
  10. What ballast adds to a delivery
  11. Frequently asked questions

What the fire code says about anchoring a tent

The International Fire Code does not give a weight per leg. It requires that a tent be designed and installed to withstand the weather and not collapse, that you can document it, and that water filled ballast be approved first. The number itself comes from the manufacturer, an engineer or the local fire official.

This is general information, not engineering or legal advice. Your tent maker's documents and your fire code official decide what is enough on a given site.

Most US jurisdictions enforce some edition of the IFC, whose Chapter 31 covers tents and membrane structures. The section numbers moved between editions:

RuleWhat it saysSource
Structural stability"Tents or membrane structures and their appurtenances shall be designed and installed to withstand the elements of weather and prevent collapsing." Documentation of structural stability "shall be furnished to the fire code official"2025 California Fire Code 3103.8, based on the 2024 IFC
Water filled vesselsPermitted "where approved and in accordance with the tent or membrane structure manufacturer's load specifications"2025 California Fire Code 3103.8.1
Engineered designTents over one story, over 7,500 square feet, or with an occupant load over 1,000 must comply with building code sections 1606 to 1609 (structural loads)2025 California Fire Code 3103.8.2 to 3103.8.4
Older wordingTents "shall be adequately roped, braced and anchored to withstand the elements of weather and prevent against collapsing", documentation "on request"2014 Indiana Fire Code 3103.9, based on the 2012 IFC
Building code linkTents erected for less than 180 days "shall also comply with the International Fire Code"2021 IBC 3103.1, per ICC

Read 16 October 2026.

What "documentation" means is set locally. Indiana's State Fire Marshal reads it as the manufacturer's or engineer's specifications for that tent; an installer without them signs an anchorage documentation form and leaves it with the event coordinator. Keep your manuals and ballast charts in the truck.

The permit threshold, usually 400 square feet, and the rest of Chapter 31 are covered in licenses, permits and inspections.

Stakes or ballast

Stake whenever the surface and the site owner allow it, and ballast when they do not. Stakes are lighter to haul and, per TentCraft's engineers, a properly installed stake equals about 200 pounds of weight. Ballast is for concrete, asphalt, pavers, rooftops and sites with buried lines.

Manufacturers lean the same way. Ohenry Tents says it "recommends staking your tent always" and treats concrete blocks as the fallback where full staking is not possible. American Tent says pole tents "should never be used with tent weights in place of staking", because a pole tent depends on stake tension. So a hard surface booking is a frame tent booking, which is why how to start a tent rental business tells new operators to price the surface.

What a staking plan looks like without engineering documents, per the Laconia, New Hampshire fire department's April 2025 bulletin:

  • Stakes at least 36 inches long and 1 inch in diameter, driven straight down with only 2 to 4 inches exposed, and webbing tied at ground level.
  • A rule of thumb of 10 pounds per square foot of tent, spread equally across the anchor points, with the installer able to show it.

Anchor Industries' F3 frame tent manual specifies 1 inch by 30 inch stakes, one per base plate, with guys staked 2 feet from the uprights, and recommends "a factor of safety of at least 2X" against all loads.

Staking is digging. Call 811 in the US before you drive stakes, as the tent rental business guide explains, and where you cannot get a locate in time, ballast instead.

How much weight per tent leg

How much weight per tent leg depends on the tent, the wind speed and the surface, so take it from your manufacturer. The two published charts we found: TentCraft rates its frame tents at 625 pounds per leg, and American Tent sets 660 pounds per leg on 20 foot wide tents and 1,320 on 30 and 40 foot wide ones.

American Tent: water ballast by tent size

American Tent sells the Giffy, a 75 gallon water barrel that weighs 30 pounds empty and 660 full, and publishes how many each frame tent needs. Wider tents use a double plate, two barrels on one leg.

Frame tentBarrelsTotal ballastPer leg, where statedSource
10x1042,640 lbNot statedAmerican Tent product page
20x2085,280 lb660 lbAmerican Tent product page and blog
20x30106,600 lb660 lbAmerican Tent product page and blog
20x40127,920 lbNot statedAmerican Tent product page
30x301610,560 lb1,320 lbAmerican Tent product page and blog
30x602415,840 lb1,320 lbAmerican Tent product page and blog
40x403221,120 lbNot statedAmerican Tent product page
40x604026,400 lb1,320 lbAmerican Tent product page and blog

Totals are barrels times 660 pounds. Read 16 October 2026; the blog is dated 1 May 2026. The product page recommends the system for frame tents 40 feet wide or smaller.

TentCraft: engineer rated frame tents

TentCraft publishes a structural analysis for each E-Series frame tent, stamped by a professional engineer in 2021 to the 2015 IBC and ASCE 7-10, all at 625 pounds per leg with a 1 inch guy strap. Four legs means 2,500 pounds per tent.

Frame tentWind rating, no wallsWind rating, with wallsBallast per legSource
10x10Up to 100 mphUp to 80 mph625 lbTentCraft E-Series page and report
15x15Up to 80 mphUp to 60 mph625 lbTentCraft E-Series page and report
20x20Up to 65 mphUp to 50 mph625 lbTentCraft E-Series page and report

Ratings are three second gusts in suburban terrain. The reports give lower figures in open terrain, down to 40 mph for an enclosed 20x20.

Ohenry Tents gives a rougher example in its frame and pole tent guide: a 20 foot wide tent "may require 300 lb. blocks at each leg", a 40 foot wide tent "1,000 lb. blocks per leg", with no wind speed attached.

Why 660 pounds does not hold 660 pounds

Ballast resists by friction and dead weight, not by grip. Laconia's bulletin warns that 800 pounds of ballast "may not provide eight hundred (800) pounds of uplift resistance". The ballast tools from the Advanced Textiles Association's Tent Rental Division, built with Clemson University, check three tent failure modes: sliding, uplift and overturn. They use measured friction for concrete blocks, plastic barrels and steel drums on smooth and rough concrete, asphalt, gravel, dirt and grass. The ATA's non engineered tool is for Tent Rental Division members; the American Rental Association publishes a tent ballasting tool built with the same association.

Local rules that set the number

Where the code leaves the number open, some fire departments write one down. Check yours before you quote a hard surface install, because a local rule can double the ballast you planned to bring, or rule out water barrels entirely.

JurisdictionRuleSource
San Francisco, CaliforniaAt least 5 lb per square foot of ballast, up to 14 where conditions require; 10 lb on Port property, Treasure Island and Yerba Buena Island. 2 inch ratchet straps, no rope. Water barrels completely filledSF Fire Department Bulletin 2.13, 2022 SF Fire Code
San Francisco, large tentsOver 5,000 square feet, over 500 occupants or a clear span over 60 feet: an engineer's installation report confirming a design wind of at least 80 mphSF Fire Department Bulletin 2.13
Laconia, New HampshireBallast of concrete or steel. Water barrels prohibited over 400 square feet unless supplementing another approved methodLaconia Fire Prevention Division, bulletin 700-2, April 2025
Laconia, New HampshireWithout wind documentation, an emergency plan that evacuates at 20 mphLaconia bulletin 700-2
IndianaInstaller signs an anchorage documentation form where no manufacturer documentation existsIndiana Department of Homeland Security, 2014 Indiana Fire Code training, rev. 2019

Read 16 October 2026.

At 5 pounds per square foot, San Francisco's minimum for a 20x40 tent is 4,000 pounds. Laconia's staking rule of thumb, 10 pounds per square foot, puts 8,000 pounds on the same tent's anchors.

Types of tent ballast and what they weigh

Rental tent ballast comes in four kinds: water barrels, concrete blocks, steel plates and, for pop up canopies only, sand or water bags. Water is light to haul and heavy once filled; concrete is heavy both ways; steel is compact but light per piece.

BallastWeightPrice read 16 October 2026Source
75 gallon water barrel (Giffy)30 lb empty, 660 lb full$948.04 for a 4 packAmerican Tent
55 gallon water barrelAbout 460 lb of water when full (our arithmetic)$20 to rentUSGS density; Big Ten Rentals, Iowa City
250 gallon water ballastAbout 2,080 lb of water when full (our arithmetic)$50 to rentBig Ten Rentals
Concrete block, 20 x 20 x 12 inches350 lb$149, or $129 each for 75 or moreBlock And Roll
Concrete block350, 500 or 700 lb$25, $25 and $40 to rentBig Ten Rentals
Concrete bunker block1,200, 2,400 or 3,000 lb$75, $150 and $150 to rentBig Ten Rentals
Steel weight, small frame or pop up58 lb$7 to rentBig Ten Rentals
Sandbag, pop up only40 lb$7 to rentBig Ten Rentals

Water arithmetic uses the USGS figure of about 62.4 pounds per cubic foot, or about 8.3 pounds a gallon.

Three cautions from the sources:

  • Standard drums. American Tent says 55 gallon drums "can slide, tip, or shift under wind loads if not properly engineered", and that some municipalities no longer allow them.
  • Improvised weights. American Tent says sandbags, bucket weights and do it yourself cinder blocks "should never be used for large or professional tent setups".
  • The connection. San Francisco requires 2 inch ratchet straps between frame and ballast and bans rope. A heavy block on a weak strap is not anchorage.

Where you buy these, and which tents come with ballast hardware, is in buying event tents.

Wind ratings and when to take a tent down

Most rental frame and pole tents have no load documentation, as Laconia's fire bulletin notes, so the evacuation speed in your weather policy is the number that protects people. Engineered tents publish one. Non engineered tents rely on the manufacturer's guidance and the conservative plan your fire official accepts.

  • TentCraft publishes engineer stamped gust ratings of 50 to 100 mph for its E-Series frame tents at 625 pounds per leg, shown above.
  • American Tent says its tents, properly secured, "can withstand winds up to 36 mph", and separately that open tents with the barrel strap can take "up to 50 mph". It advises taking the tent down when high winds are forecast.
  • Anchor Industries says evacuation is recommended "if threatening or windy weather occurs", with no speed given.
  • Eureka states its traditional party canopies are not engineered or wind rated.
  • Laconia's bulletin offers, for tents with no wind documentation, an emergency plan that evacuates at 20 mph.

Sidewalls change everything. TentCraft's 20x20 drops from 65 mph to 50 with walls, so a tent closed up for a cold night, as in heated tent rentals, needs its rating checked with walls on. Write the evacuation speed into your agreement and tell the customer at setup, the same way the wind policy works in bounce house safety.

The wind check reads the hourly gust forecast for the party's ZIP code against a limit you set, so put in the tent's evacuation speed and it flags the hours that come close. Ballast starts from the tent's size, and the tent size calculator gives that size from a guest count.

How to anchor a tent on concrete or asphalt

To anchor a tent on concrete, use a frame tent, set the manufacturer's ballast at every leg, and connect it with rated ratchet straps. Never drill into a surface without the owner's written permission, and keep the ballast chart with you for the fire official.

  1. Confirm the surface at booking. Concrete, asphalt and pavers mean a frame tent and ballast, and a quote that includes it.
  2. Check the local rule. Ask whether water barrels are approved and whether a pounds per square foot minimum applies.
  3. Take the manufacturer's chart, or an engineer's plan for anything over 7,500 square feet.
  4. Load the right ballast for every leg, corners included, plus spares.
  5. Set the frame, then the ballast at each leg, in the position the maker specifies.
  6. Strap frame to ballast with rated 2 inch ratchet straps, never rope.
  7. Fill water ballast completely, as San Francisco requires.
  8. Drill only with permission. Drilled anchors and eyebolts exist for pavement, but they damage the surface; get the owner's written approval and the right anchor for the slab.
  9. Leave the paperwork with the event contact: the chart, your evacuation speed and, in Indiana, the anchorage form if you have no manufacturer documentation.

Canopy tent weights: the 10x10 question

A 10x10 pop up canopy needs weights on every leg, and most farmers markets require 40 pounds per leg. Manufacturers start lower for calm days: E-Z UP from 22 pounds per leg, Westshade 25 to 40. TentCraft's own rating is 200 pounds in total for 40 mph.

Canopy guidanceWeightWindSource
E-Z UPFrom 22 lb per leg for smaller canopies in mild conditionsLight duty frames 10 to 15 mph; heavy duty 25 to 30 mphE-Z UP FAQ
Westshade, 10x1025 to 40 lb per leg as a general rule; 50 to 75 lb at 15 to 25 mphTake down above 30 mphWestshade, 19 September 2025
Westshade, 10x2060 to 100 lb per leg at 15 to 25 mphTake down above 30 mphWestshade
TentCraft, 10x10200 lb total40 mph ratingTentCraft
TentCraft, 10x20 (six legs)370 lb total35 mph ratingTentCraft, 2 February 2025
Larimer County Farmers' Market40 lb per leg, or the tent comes downNot statedLarimer County

Read 16 October 2026.

For a rental company, a canopy without weights is an incomplete rental. Send weights with every pop up you rent, and list them on the order so they come back.

Canada

In Ontario, tents are governed by the Ontario Building Code, which exempts a tent or group of tents from a permit only when it is no more than 60 square meters (about 646 square feet), not attached to a building and more than 3 meters from other structures. Larger tents need a building permit from the municipality.

Section 3.14 of Division B covers tents. It requires tents to stand at least 3 meters from the property line and tent fabric to be certified to CAN/ULC-S109 or NFPA 701, as the Town of Innisfil's 2023 summary sets out. Ask the building department what anchorage documentation it wants with the permit application.

Locates are slower than in many US states: Ontario Dig Authority, formerly Ontario One Call, asks for a request at least 5 business days before you dig. Other provinces run their own locate services and fire codes, so confirm both before your first install there.

What ballast adds to a delivery

Ballast turns a tent install into a heavy haul. A 40x60 on American Tent's chart needs 26,400 pounds of water ballast: 1,200 pounds of empty barrels on the truck and about 3,000 gallons of water at the site. The same weight in 350 pound concrete blocks is about 76 blocks on the truck.

That arithmetic drives three decisions:

  1. Water or concrete. Water barrels travel light but need a water source and time to fill and drain; ask for the spigot when you book. Concrete needs no water but every pound rides both ways.
  2. Crew time. Every block or barrel is placed, strapped and recovered by hand. Price hard surface installs separately from staked ones, as how to start a tent rental business recommends.
  3. Truck capacity. Concrete for one large tent can exceed a light truck's payload before the tent itself is loaded.

Operators who rent ballast price it per piece. Big Ten Rentals in Iowa City lists blocks from $25 and bunker blocks up to $150; KJ Event Rentals starts at $40 a block, "subject to labor charge".

Tent rental software helps with the weight as well as the calendar. In Rentopus each item can carry its packed weight, and the pull sheet adds up what each truck carries. List ballast as its own item with its weight and it counts on the pull sheet when it is on a booking. When a route's deliveries weigh more than the payload you set for that truck, the route screen warns you to move a stop. At checkout the customer says what the ground is, and an item you have not ticked for that surface, a pole tent marked grass only for instance, is refused with a message.

Rentopus is booking, delivery and payment software for party rental companies. Your availability, your booking website and your signed agreements in one place, so two customers are never promised the same unit on the same Saturday. See how it works · Browse the guides

Frequently asked questions

How much weight do you need per tent leg?

It depends on the tent and the wind it is rated for, so use the manufacturer's chart. TentCraft rates its 10x10 to 20x20 frame tents with 625 pounds per leg. American Tent uses 660 pounds per leg on 20 foot wide frame tents and 1,320 on 30 and 40 foot wide ones. A 10x10 pop up canopy needs far less: most markets require 40 pounds per leg.

What are tent weights?

Tent weights are ballast placed at each leg to hold a tent down where stakes cannot go, such as concrete, asphalt or pavers. For rental frame tents they are water barrels of up to 660 pounds, concrete blocks of 350 pounds and up, or steel plates. For pop up canopies they are sand or water bags of roughly 20 to 50 pounds per leg.

How do you anchor a tent on concrete?

Use a frame tent, not a pole tent, and set the manufacturer's ballast at every leg, strapped to the frame with rated ratchet straps. Check whether your fire official approves water barrels and whether a pounds per square foot minimum applies. Never drill into the surface without the owner's written permission, and keep the ballast chart for the inspector.

How much does a 55 gallon water barrel weigh full?

About 460 pounds of water, using the USGS density of about 62.4 pounds per cubic foot, plus the barrel itself. American Tent's 75 gallon Giffy barrel weighs 660 pounds full and 30 empty. Some jurisdictions restrict water barrels: Laconia, New Hampshire prohibits them on tents over 400 square feet unless they supplement another approved method.

Does the fire code require tent ballast?

The International Fire Code requires tents to be designed and installed to withstand the weather and not collapse, with documentation for the fire official, and allows water filled ballast only where approved and per the maker's load specifications. It does not set a weight. Some fire departments do: San Francisco requires at least 5 pounds per square foot.

Can you use sandbags to hold down an event tent?

Not for a large or professional tent. American Tent says sandbags, bucket weights and homemade cinder blocks should never be used for large or professional setups, and a 40 pound sandbag is a small fraction of the 625 to 1,320 pounds per leg that manufacturers chart for frame tents. Sandbags belong on pop up canopies, where markets typically require 40 pounds per leg.

Is a stake or ballast better for a tent?

A stake, where the ground and the site owner allow it. Ohenry Tents recommends staking always, and TentCraft's engineers count one properly installed stake as about 200 pounds of weight. Ballast is for hard surfaces and sites where you cannot get a utility locate in time. Pole tents need stakes: American Tent says they should never use weights in place of staking.

What wind speed should you take a tent down?

Follow the manufacturer's rating for that tent with or without walls. Most frame and pole tents have no wind documentation, and American Tent says its secured tents withstand winds up to 36 mph. Laconia, New Hampshire accepts an emergency plan that evacuates at 20 mph for tents with no wind documentation. Put one evacuation speed in your agreement and tell the customer at setup.

Sources

  • International Code Council, 2024 International Fire Code Chapter 31, as adopted in the 2025 California Fire Code (Title 24, Part 9), section 3103, read 16 October 2026 via GoCodebook
  • Indiana Department of Homeland Security, "Anchorage Required", 2014 Indiana Fire Code section 3103.9 training and anchorage documentation form, rev. 1 January 2019
  • International Code Council, Significant Changes to the IBC, 2021 Edition, section 3103.1
  • San Francisco Fire Department, Bulletin 2.13, Submittal Requirements for Temporary Tents and Membrane Structures, read 16 October 2026
  • City of Laconia Fire Prevention Division, "Tent Installation and Inspections", bulletin 700-2, April 2025
  • Advanced Textiles Association, Tent Rental Division, "Ballasting Tools: The Industry Standard", webinar, 18 January 2023, and Ballasting Tools page, updated 24 June 2026
  • American Rental Association, Tent Ballasting Tool page, read 16 October 2026
  • American Tent, Giffy Tent Ballasting System product page, read 16 October 2026, and "How to Choose the Right Commercial Tent Weights for Your Canopy", 1 May 2026
  • TentCraft, E-Series frame tent page and structural analysis reports by Trison Engineering Group, July and August 2021, read 16 October 2026
  • TentCraft, "How Much Weight Is Needed to Hold Down a 10x20 Canopy Tent?", 2 February 2025
  • Ohenry Tents, "Frame Tent Vs. Pole Tent" guide, 2025
  • Anchor Industries, F3 Frame Tent installation instructions
  • Eureka, Technical Instruction Manual: Traditional Party Canopies
  • Block And Roll, 350 lb tent ballast block, read 16 October 2026
  • Big Ten Rentals, Iowa City, tent ballast rental page, read 16 October 2026
  • KJ Event Rentals, tent ballast block, read 16 October 2026
  • US Geological Survey, Water Science School, "Water Density", read 16 October 2026
  • E-Z UP, support FAQ, read 16 October 2026
  • Westshade, "How Much Weight to Hold Down a 10x20 Canopy Tent", 19 September 2025
  • Larimer County Farmers' Market, vendor resources, read 16 October 2026
  • Town of Innisfil, "Ontario Building Code: Tent Requirements", 2023
  • Ontario Dig Authority, home page, read 16 October 2026